Basic Info.

Model NO.
YBM 12/0.4
Shell Material
Steel Plate
Shell Protection Grade
IP30
Brand
Kunji
Rated Voltage
10 to 35 Kv
Rated Capacity
100 to 2000kVA
OEM
Offered
Enclosure Temperature Rise Level
10K
Noise Level
≤50dB
Transport Package
Iron Case/Wooden Case
Specification
Customization
Trademark
kunji elctric
Origin
Zhejiang, China
HS Code
8537209000
Production Capacity
50pieces/Month

Product Description

Steel Plate Type Outdoor Pre-Installed Substation




 

Product Description

Steel Plate Type Outdoor Pre-Installed Substation Grid Substation Mobile Substation
 

(1) Box shell

European box change box shell with steel structure as the main body, four sides can be used according to different use environment can be composite sandwich plate, stainless steel plate, cold rolled plate, stainless steel plate inlaid anti-corrosion wood, concrete wall, so as to achieve coordination with the environment.
 

(2) high-voltage chamber

High voltage inlet cabinet, high voltage outlet cabinet, high voltage metering cabinet, PT cabinet, DC screen and other devices are installed in European box transformer high voltage switchgear mainly to XGN15-12 type ring network cabinet and XGN-12 type inflatable cabinet, simple operation, safe use.

 

(3) Transformer room

European-style box transformer room is equipped with dry type transformer or oil-immersed transformer, temperature controller and high-power fan are installed indoors. The high-voltage end of transformer is connected by cable, the low-voltage end is connected by high-quality copper bar, and the exposed part is wrapped by insulating sleeve.

 

(4) low-voltage chamber

European-style box transformer low-voltage chamber mainly uses GGD low-voltage switchgear, according to the demand can be configured with low-voltage inlet line, low-voltage metering, low-voltage compensation, low-voltage outlet switchgear, can realize intelligent control, without special guard.

 

(5) Principle

The principle of European box-type substation is basically the same as that of traditional civil power room. The high-voltage power supply comes in through high-voltage switchgear, goes through transformer step-down, and then distributes electric energy through low-voltage switchgear. Because European box-type substation adopts box shell structure, it can be strong mobility, easy installation, and can be used outdoors.

Technical Parameters
 

High voltage chamber Description Unit Arguments
  Rated frequency HZ 50
  Nominal voltage KV 6 10 35
  Maximum operating voltage KV 6.9 12 40.5
  Rated current A 400,630,1250
  Transfer current A 1200-2000
  Rated short time current KA 12.5(2s/4s),16(2s/4s),20(2s/4s)
  Rated peak tolerable current KA 31.5,40,50
  Power frequency withstand voltage - to ground and time/isolation fracture KV 32/36 42/48 95/118
  Lightning Strike - to ground and time/isolation fracture KV 60/70 75/85 185/215
  Rated short-circuit breaking current (current limiting fuse) KA 31.5
  Switch off no-load transformer capacity KVA 2500
Transformer  Rated capacity KVA 30-2500
 
 Tap range
% ±2*2.5%,±5%
  Linkage group   Yyn0,Dyn11
  Impedance voltage % 4,4.5,6,8
  Nominal voltage V 220,380,690,800

              Low voltage chamber

Rated current of main loop A 50-4000
  Branch current A 5-800
  The main circuit is rated to withstand short-time current KA 15(1s),30(1s),50(1s),65(1s)
  Rated peak tolerable current of main loop KA 30,63,110
shell Protection class (conventional products)   IP33
  Noise level dB ≤50
  Enclosure temperature rise level   10K

Steel Plate Type Outdoor Pre-Installed Substation

WORKING CONDITIONS 

1. Altitude: no more than 2000M.

 

2. Ambient temperature: high temperature: +40ºC; Low temperature: -45ºC : high monthly average temperature: +30ºC : high annual average temperature: +20ºC;

 

3, installation environment: no explosive, corrosive liquid, gas and dust, installation site without violent shock, allowed in a certain period of time Or run completely submerged in water.

 

4. Ground acceleration induced by earthquake Ag; The horizontal direction is lower than 3m/s; The vertical direction is lower than 1.5m/s.

 

5, the waveform of the power supply voltage: approximately sine wave.

 

6, three-phase power supply symmetry: for three-phase underground transformer, three-phase power supply voltage should be roughly symmetrical.


 



PRODUCTION DETAILS

Steel Plate Type Outdoor Pre-Installed SubstationSteel Plate Type Outdoor Pre-Installed Substation
Steel Plate Type Outdoor Pre-Installed Substation
Steel Plate Type Outdoor Pre-Installed Substation

Company Profile

Steel Plate Type Outdoor Pre-Installed Substation

Kunji Electric Co., Ltd. which is specialized in producing, developing and marketing power transmission and distribution products. The company is established in 2015, which is located in Wenzhou city, Zhejiang province, China.
Our main products are including switchgear, ring main unit, transformer,substation, and Other Power Transmission & Transformer. Our product has passed ISO9001 and CE certificate.
We have a professional technical team which can provide you with full design solution and technical support.


Workshop

Steel Plate Type Outdoor Pre-Installed Substation
Cr
ertifications

Steel Plate Type Outdoor Pre-Installed Substation


Packaging & Shipping


Steel Plate Type Outdoor Pre-Installed Substation

Steel Plate Type Outdoor Pre-Installed Substation

FAQ
1. Are you a trading company or manufacturer ?
    We are a professional  factory with  10 years experience in the field of High and low Voltage switchgears, Substation,transformers,
cable distribution box and various electrical equipment.
    Our factory is the excellent supplier of State Grid Corporation od China.
2. Do you accept customized serveice ?
    We offer  OEM/ODM service , can print your logo on product . our  professional technical and quotation team can provice a satisfied satisfied project according to your drawing and parameters .
3. What is your MOQ?
    Our MOQ is 1 piece.  
4. How long is your delivery lead time ?
    It depends on your  product requirement and quantity . Generally , 5~10  working days is avaliable .
5. How do you solve quality problems?
    Please porvide detailed photoes of quality problems.  our technical  and quality testing department  will analyse.we will make a satisfied soluton within 2 days .
6. What is your payment terms ?
    30%T/T in adcance,70% before shipment .  West union,L/C are also acceptable .



 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Diamond Member Since 2023

Suppliers with verified business licenses

Manufacturer/Factory, Trading Company
Registered Capital
30000000 RMB
Plant Area
501~1000 square meters