Yb Series 10kv 200kVA~2000kVA Outdoor Compact Transformer Substation European Style Substation
Technical Parameters
High voltage chamber | Description | Unit | Arguments |
Rated frequency | HZ | 50 | |
Nominal voltage | KV | 6 10 35 | |
Maximum operating voltage | KV | 6.9 12 40.5 | |
Rated current | A | 400,630,1250 | |
Transfer current | A | 1200-2000 | |
Rated short time current | KA | 12.5(2s/4s),16(2s/4s),20(2s/4s) | |
Rated peak tolerable current | KA | 31.5,40,50 | |
Power frequency withstand voltage - to ground and time/isolation fracture | KV | 32/36 42/48 95/118 | |
Lightning Strike - to ground and time/isolation fracture | KV | 60/70 75/85 185/215 | |
Rated short-circuit breaking current (current limiting fuse) | KA | 31.5 | |
Switch off no-load transformer capacity | KVA | 2500 | |
Transformer | Rated capacity | KVA | 30-2500 |
Tap range
|
% | ±2*2.5%,±5% | |
Linkage group | Yyn0,Dyn11 | ||
Impedance voltage | % | 4,4.5,6,8 | |
Nominal voltage | V | 220,380,690,800 | |
Low voltage chamber |
Rated current of main loop | A | 50-4000 |
Branch current | A | 5-800 | |
The main circuit is rated to withstand short-time current | KA | 15(1s),30(1s),50(1s),65(1s) | |
Rated peak tolerable current of main loop | KA | 30,63,110 | |
shell | Protection class (conventional products) | IP33 | |
Noise level | dB | ≤50 | |
Enclosure temperature rise level | 10K |
WORKING CONDITIONS
1. Altitude: no more than 2000M.
2. Ambient temperature: high temperature: +40ºC; Low temperature: -45ºC : high monthly average temperature: +30ºC : high annual average temperature: +20ºC;
3, installation environment: no explosive, corrosive liquid, gas and dust, installation site without violent shock, allowed in a certain period of time Or run completely submerged in water.
4. Ground acceleration induced by earthquake Ag; The horizontal direction is lower than 3m/s; The vertical direction is lower than 1.5m/s.
5, the waveform of the power supply voltage: approximately sine wave.
6, three-phase power supply symmetry: for three-phase underground transformer, three-phase power supply voltage should be roughly symmetrical.